EN
If the total power consumption over the rated power of the inverter,
remove the non-critical: loads until the total power consumption is
below the rated power.
4-4. Switch ON Inverter
Set the power switch to the "ON" position. The inverter will carry
out self-diagnosis and, the LED's will also appear various colors.
Set the power switch to the "OFF" position. The inverter stops and
all the lights that are on will go off.
4-5. Protection Mechanism
4-5-1. SE200 Protection Mechanism
Model
12V
24V
Model
12V
24V
4-5-2. SE350 protection mechanism
Model
12V
15.5V ± 0.25V
24V
48V
Model
12V
24V
48V
22
Over Voltage (DC)
Shutdown
Restart
16V ± 3%
14.5V± 3%
32V ± 3%
29V ± 3%
Table 20. SE200 DC input protection mechanism
Over Temperature Protection
Shutdown
90 ± 3℃
Table 21. SE200 over temperature protection mechanism
Over Voltage (DC)
Shutdown
Restart
14.5V± 0.25V
31V ± 0.5V
29V ± 0.5V
62 ± 1V
58V ± 1V
Table 22. SE350 DC input protection mechanism
Over Temperature Protection
Shutdown
83 ± 5℃
Table 23. SE350 over temperature protection mechanism
Under Voltage
Alarm
Shutdown
10.5V ± 3%
10.0V ± 3%
21V± 3%
20V ± 3%
Restart
50 ± 3℃
Under Voltage
Alarm
Shutdown
10.5V ± 0.25V
10V ± 0.25V
21V± 0.5V
20V ± 0.5V
42V± 1V
40V ± 1V
Restart
53 ± 5℃
Under Voltage
Restart
12.5V ± 3%
25V ± 3%
Under Voltage
Restart
12V± 0.25V
24V ± 0.5V
48 ± 1V