Connecting The 120 V Room Thermostat; Connecting The 24 V Room Thermostat - Dunkirk DCC-150 COMBI Manuel D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

TERMINAL BLOCK M1
(L) = Live (brown)
(N) = Neutral (light blue).
= Ground (yellow-green).
(1) (2) = contact for 120V Room Thermostat.
Put back the jumper on terminals 1-2 of boiler terminal
block M1 if the room thermostat is not used or if the
Remote Control is not installed.
TERMINAL BLOCK M2
Terminals 1 - 2: bus connection of programmable room unit
(supplied as an accessory)
Terminals 4 - 5: outdoor temperature sensor connection (supplied as an accessory)
Terminal 3 : not used.
Terminals 6 - 7 - 8: see section 11.1 and 11.2
Terminals 9 - 10: Indirect storage tank sensor connection for Dunkirk Boiler DCB-125
model.
WARNING
If the appliance is connected to an infloor system, install a limit thermostat to prevent the latter from overheating
IMPORTANT INFORMATION
Use the relative cable grommets at the bottom of the boiler to thread the cables through to the terminal blocks.

11.1 CONNECTING THE 120 V ROOM THERMOSTAT

DANGER
HIGH VOLTAGE - The connections in terminal block M1 are high voltage (120 V). Before making connections, make
sure the appliance is disconnected from the power supply. Respect polarity L (LIVE) - N (NEUTRAL).
To connect the 120V Room Thermostat to the boiler, proceed as described below:
• switch off the boiler;
• access the terminal block M1;
• remove the yellow jumper on terminals 1 & 2 of the M1 bus.
• remove the jumper from the ends of contacts 1-2 and connect the wires of the 120 V Room Thermostat;
• switch on the boiler and make sure the Room Thermostat works correctly.

11.2 CONNECTING THE 24 V ROOM THERMOSTAT

To connect a 24 V Room Thermostat proceed as follows:
• switch off the boiler;
• access the terminal block M2;
• connect the wires of the 24 V Room Thermostat to the terminals 6(R)-7(W)-8(C);
• switch on the boiler and make sure the 24 V Room Thermostat works correctly.
NOTE: the maximum load admitted is 10 mA
To connect a 24 V Heat anticipator Room Thermostat proceed as follows:
• switch off the boiler;
• access the terminal block M2;
• connect the wires of the 24 V Heat anticipator Room Thermostat to the terminals 6-7;
• connect a bridge between the terminals 6-8;
• switch on the boiler and make sure the 24 V Heat anticipator Room Thermostat works correctly.
M2
M1
27
1
2
3
4
5
R
Bk
6
W
R
7
lB
8
C
9
10
M2
1
2
3
4
5
Bk
6
R
7
lB
8
9
10
M2
240011373, Rev. G [03/31/2017]
24V