Installation Site - Steibel Eltron LWE 40 Installation

Appareil de ventilation décentralisée avec récupération de chaleur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INsTALLATIoN
preparation
4.2

Installation site

WARNING Electrocution
If installing the appliance in rooms with a bath and/or
shower, take the relevant safety zone into account in
accordance with the information on the appliance type
plate. The safety zones are defined in the IEC 60364-7-
701 standard.
If a pair of appliances working in differential mode are being
installed in two different rooms in the apartment, create an air
connection between these rooms by ensuring that the overflow
air apertures are large enough.
Windowless extract air areas (e.g. kitchens, bathrooms and toilets)
should only be ventilated with the appliance if it is installed in an
external wall. Appliances should not be connected to a shaft or
pipeline.
Installation in basement rooms with light wells is not permissible,
as recirculation of exhaust air cannot be prevented.
To avoid draughts caused by fan operation, we recommend in-
stalling the appliance next to windows at lintel height.
Wall thickness including render/plaster
20
LWE 40 TG-550
A
mm
300-550
Minimum clearances
Note
Take the position of the core hole into account when de-
signing the interior fittings, e.g. kitchen cabinets.
- Ensure a clearance of 350 mm between the side of the inter-
nal panel and any furniture.
- Inside the building, ensure there is enough free space in
front of the internal panel for inserting and removing the fan
unit.
- Never install the appliance near seating areas or at the head
of a bed.
- Ensure a clearance of 100 mm from all sides of the external
panel to downpipes, balconies and other solid objects.
www.stiebel-eltron.com
A
LWE 40 TG-800
550-800
A 220  mm
B 220  mm
S Specified clearance depending on the structural condition of
the wall
We recommend positioning the upper edge of the internal panel
30 mm beneath the upper edge of the window.
Clearances between appliances working in differential mode
Appliances working as a pair in differential mode must be installed
with a minimum horizontal and vertical clearance.
A
S
B
y
1000 mm
LWE 40 |
23