Normal Operation; Burner Start-Up Cycle - Riello Burners 40 G5R Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FAILURE DETECTION ON HEATING DEVICE

NORMAL OPERATION

The plug fitted in the panel is placed in the position
corresponding to "Resistance ON"
drawing on the right).
When the remote control closes, the LED lights up
and, after about two minutes, the burner starts up.
BURNER DOES NOT OPERATE
1) If the LED is OFF, the heating resistance placed
in the nozzle-holder is off.
2) If the LED is ON and nevertheless the burner
does not run, place the plug in the position cor-
responding to "Resistance OFF"
drawing on the right) .
If the motor runs, the delaying device inside the
control box is out of order.
3) If the motor does not run, it means that the fail-
ure is neither in the panel nor in the resistance,
but elsewhere.

BURNER START-UP CYCLE

Normal
Thermostat
Resistance
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
2347
All manuals and user guides at all-guides.com
~
~
120s
12s
CONTROL BOX 531SE
PLUG
(see
Resistance ON
PLUG
(see
Resistance OFF
Lock-out, due to light-failure
~
120s
8
GB
*
S7059
LED
S7060
LED
~
~
12s
5s
D5329

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

3744612

Table des Matières