4. Heat generators for reheating
The LATENTO XXL is primarily charged with free solar heat. However, if there is
not enough solar energy, other heat generators can be utilized for reheating. To
guarantee sufficient hot water supply, the supply of the heat generator must have
at least a 15 °C higher temperature than the desired hot water temperature, min.
75 °C flow temperature of the heat generator).
Potential Heat generators for Reheating:
Elec. heating element
Installation proposal A in the LATENTO catalogue
Boiler unit with high flow temperature (min. 60 °C)
Installation proposal B in the LATENTO catalogue
Low-temperature boiler
Installation proposal C in the LATENTO catalogue
Boiler unit with high flow temperature, with additional solid material Installation
Installation proposal D in the LATENTO catalogue
Low-temperature boiler with additional solid material boiler
Installation proposal E in the LATENTO catalogue
Pellets boiler
Installation proposal F in the LATENTO catalogue
District heating
Heat pump
Installation proposal G in the LATENTO catalogue
26