Electrical Connection; Connection Sequence - Schaudt LAS 1218-2 Notice D'utilisation Et De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Connection sequence

810.523 BA / EN
Heruntergeladen von
manualslib.de
Instruction Manual and Installation Instructions LAS 1218-2
80
90
4 x attachment-
holes, ø4.5
Fig. 1
2.2.2
Fuse holder
For applications that require one or two additional fuses (see sections
1.1.1.2 and 1.1.1.3 for example), fuse holders from the connector set must
be installed.
Determine the place of installation of the fuse holder(s). The place of in-
stallation must be in the direct vicinity of the corresponding battery.
Drill a hole 8mm in diameter for every fuse holder.
Lock the fuse holder into place in the drillhole.
2.3

Electrical connection

The battery charger connection is established in the following order:
1. All connections on the front panel of the battery charger
2. Battery lines to the battery terminals
3. 230V mains connection
Disconnecting
Disconnect in the reverse order.
2.3.1
Connections on the front panel
ATTENTION!
Y
Short circuits!
Damage to the battery charger or fire damage to cable:
F
Handbücher-Suchmachiene
Dimension diagram of LAS 1218-2 battery charger (dimensions in mm)
To protect the supply lines in the event of a short circuit, connect the
fuses directly to the positive terminal of battery.
Date: 06.11.2014
247,5
163,5
Flat pins 6.3 x 0.8
in the insulation housing
9