Télécharger Imprimer la page

Festo CPX Serie Manuel D'utilisation page 17

Masquer les pouces Voir aussi pour CPX Serie:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2.1 Significance of the LED statuses
LED
Behaviour and significance
PS
– Illuminated green: operating voltage U
– Flashes green: undervoltage U
– Off: operating voltage U
PL
– Illuminated green: load voltage U
– Flashes green: undervoltage U
– Off: load voltage U
P
– Illuminated red: CPX starting or CPX error
– Off: CPX communication OK
X1 ... X4
– Illuminates green: device OK
– Flashes green: diagnostics
– Illuminated red: I-port error
– Flashes red: configuration error
– Off: no device detected
Festo CPX-CTEL-Z6 1601b English
EL/SEN
too low or not applied
EL/SEN
VAL
VAL
not applied or not used
VAL
OK
EL/SEN
OK
17

Publicité

loading

Ce manuel est également adapté pour:

Cpx-ctel-4-m12-5pol