2- 7 M6 - EJPT setup
It permits to activate the remote start if the inputs J4.4 is closed to negative. In this case, after a "Start delay" time, the remote start
output is activated and, when the generator is within the limits, after "KG delay" the mains contactor is opened and the generator
contactor is closed.
When the input is open, if the mains is present the load is passed to the mains (opening of KG and closure of KR) then, after the
cooling time, the remote start output is removed.
If an alarm about the generator occurs, the management follows the programmation of parameter "E - No KR with EJPT":
a)
If No KR with EJPT is set to Off: KG is opened and the load passes to the mains, with closure of KR. The remote start
output remains active (if the active alarm is not set for genset stopping).
b)
If No KR with EJPT is set to On: KG is opened but the load is not passed to the mains. The remote start output remains
active (if the active alarm is not set for genset stopping).
POS.
NAME
A
EJPT Enable
B
Start delay
C
KG delay
D
EJPT 2 input
E
No KR with EJPT
F
Off delay
2- 8 M7 - Counters
POS.
NAME
A
Run hours
B
KG hours
C
KR hours
D
Counter reset
2- 9 M8 - Measures
The measures setup allows to adjust the measured values for genset and mains voltages. For each measure it's possible to set an
offset with 0.1V.
POS.
NAME
A
Offset VRG
B
Offset VSG
C
Offset VTG
D
Offset VRM
E
Offset VSM
F
Offset VTM
"G"=Generator, "M"=Mains
VERSO 50_v1.0.27_EN
If ON the function is enabled, if OFF the function is disabled.
It is the delay time that elapses when the input J4.4 closes to
negative before the activation of the remote start output.
It is the delay time that elapses after the starting of the generator
before the opening of KR and the closure of KG.
Function disabled in the VERSO 50 with only 1 input.
If ON, when EJPT mode is active (remote start input active), the
mains contactor opens and it's not possible to close it also if the
generator is stopped by an alarm.
It is the delay time during which the EJPT signal must be disabled to
permit the stopping of the generator and the switchin on the mains.
Here you can set a value of the work hours, then confirm the
parameter D to set the actual work hours to this value.
Here you can set a value of the work hours with KG closed, then
confirm the parameter D to set the actual work hours with KG closed
to this value.
Here you can set a value of the hours with KR closed, then confirm
the parameter D to set the actual hours with KR closed to this value.
Confirm this parameter to set the values at parameters A, B and C.
RANGE OF VALUES
Offset
Adjusted value
33502027401_3_1
DESCRIPTION
DESCRIPTION
-100 +100 (V/10)
-100 +100 (V/10)
-100 +100 (V/10)
-100 +100 (V/10)
-100 +100 (V/10)
-100 +100 (V/10)
RANGE OF
DEFAULT
VALUES
SETTINGS
On/Off
On
0-59 [min]
0
0-59 [min]
0
On/Off
Off
On/Off
Off
0-59 [s]
10
RANGE OF
DEFAULT
VALUES
SETTINGS
0-999999 [h]
0
0-999999 [h]
0
0-999999 [h]
0
OK
-
DEFAULT SETTINGS
0
0
0
0
0
0
page 19/24