2- 6 M5 - Alarms list
You will see a general screen for the setup of the alarms, composed by 4 pages. In the first page, select and confirm the parameter
"a" to choose the code of the alarm. In the upper part of the screen you will see the name of the correspondant alarm. Then modify
the parameters from "d" to "l" as you prefer. Return then to the first page and confirm the parameter "c" to save the modifications.
For every alarm, you can program all the following parameters:
POS.
NAME
Select this parameter to choose the alarm that you want to set. All the parameters in the
A
Alarm code
next pages refer to the alarm selected in this parameter. In the upper part of the screen
you will see also the name corresponding to the code that you are selecting.
Category of
B
Not selectable parameter.
the alarm
Parameter that has to be confirmed with the "i" button to save all the parameters from D to
C
Save alarm
L in the configuration of the alarm selected at parameter A.
It permits to choose when the alarm condition must be verified and make the alarm
D
Activation
appear: Always (always enabled), Run (active only with engine running) or Disabled
(disabled).
E
Delay
Before the activation of the alarm, the cause must remain present for this time.
Choose if the alarm must be retentive (ON: the alarm indication remains on display until
F
Retentive
you press the reset button, even if the cause has disappeared) or not (OFF: the alarm
indications disappears when the cause disappears).
Select the action in consequence of the activation of the alarm: Warning (only indication),
G
Action
Stop (the alarm stops the engine immediately) or Cooling (the alarms stops the engine
with cooling).
H
Siren
Function not available.
I
SMS
Function not available.
J
Global 1
If On, the alarm activates the output set as Global alarm 1 (if present).
K
Global KG
If On, if the alarm is active KG cannot be closed.
L
Global KR
If On, if the alarm is active KR cannot be closed.
VERSO 50_v1.0.27_EN
DESCRIPTION
33502027401_3_1
RANGE
-
-
-
Always
Run
Disabled
0-255 [s]
ON
OFF
Warning
Stop
Cooling
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
page 17/24