Télécharger Imprimer la page

Kohler SDMO VERSO 50 Manuel D'utilisation page 44

Inverseur de sources

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
2- 2 M1 - Mains setup
Selecting the mains setup you access directly to the programmation parameters about the mains, like voltage and frequency limits.
All these parameters are shown in the following table:
POS.
NAME
A
Mains rated V
B
Mains high V
C
Mains low V
D
Mains rated F
E
Mains high F
F
Mains low F
G
KR delay
H
Mains OK
I
Faulty mains
J
System type
K
Start delay
L
Stop delay
M
KR alarm ON
N
Neutral
VERSO 50_v1.0.27_EN
DESCRIPTION
Allows you to set the rated voltage.
You can set the high threshold voltage; if the voltage
measured is higher than this value, the mains is
considered faulty and VERSO 50 activates the remote
start output (in automatic mode).
You can set the low threshold voltage; if the voltage
measured is lower than this value, the mains is
considered faulty and VERSO 50 activates the remote
start output (in automatic mode).
Allows you to set the rated frequency.
You can set the high frequency threshold; if the frequency
measured is higher than this value, the mains is
considered faulty and VERSO 50 activates the remote
start output (in automatic mode).
You can set the low frequency threshold; if the frequency
measured is lower than this value, the mains is
considered faulty and VERSO 50 activates the remote
start output (in automatic mode).
You can set a delay time for the closure of the mains
contactor. This time starts from when the VERSO 50
opens
the
generator
contactor
function).
It is the delay time after which, if the mains returns within
the limits set (see parameters B, C, E, F), it's considered
stable and the mains contactor is closed, then the remote
start output is deactivated (in automatic mode).
It is the delay time after which the mains is considered
faulty, compared with the limits specified in parameters B,
C, E, F. This parameter is used to filter any temporary
instability of the mains.
You can set the type of system.
If you set it to Monophase, the system is considered as
single-phase.
If you set it to Threephase, the system is considered as
three-phase.
Delay time to activate the remote start output in automatic
mode when faulty mains conditions are true.
Delay time to remove the remote start output in automatic
mode when mains within limits conditions are true. Load
switching on mains side does not wait this delay.
If On, the alarms set as "Global KR" cause the opening of
the mains contactor.
If On, the mains is considered with neutral connected. If
Off, the mains is considered without neutral.
33502027401_3_1
RANGE OF
VALUES
0-600 [Vac]
100-200 [%]
70-100 [%]
50-60 [Hz]
100-200 [%]
0-100 [%]
0-100 [s]
(software
interlock
0-9999 [s]
0-600 [s]
Monophase -
Threephase
0-59 [s]
0-59 [s]
On-Off
On-Off
DEFAULT
DEFAULT
3-phase
1-phase
400
230
113
113
80
80
50
50
110
110
90
90
1
1
10
10
5
5
Threephase Monophase
0
0
0
0
Off
Off
On
On
page 12/24

Publicité

loading