Télécharger Imprimer la page

DURAVIT Vero Air 760418 Notice De Montage page 7

Masquer les pouces Voir aussi pour Vero Air 760418:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 8
Electrical installation
Power supply
Circuit breaker
RCCB
Pre-Installation
> Installing a permanent power supply line:
Install separate circuit breaker and residual-current
circuit breaker (RCCB) upstream
Connect all pole disconnector mains switches up-
stream located outside specified protection zones (0
- 2)
Leave 3 000 mm of feed cable exposed
> Lay equipotential bonding cables:
Leave 3 000 mm of cable exposed
10
Connect whirltub
Malfunctions due to incorrect
NOTICE
installation
> Do not fasten the cables together with cable ties.
> Do not install the supply line parallel to the control
cables.
I
Connect the supply line to the mains supply socket.
II
Connect the potential equalisation cable to the
whirltub.
76xxx xx x xx00: 50 Hz, 220 - 240 V AC
76xxx xx x xx06: 60 Hz, 220 - 240 V AC
I
= 16 A
N
I
≤ 30 mA
ΔN
Safety areas in accordance with DIN VDE 0100-701
0
6 0
1
0
I
L
N
PE
II
6 0
0
2
* or the height of
the highest shower
head / water outlet
that is permanently
installed, depending
on which is higher
WH_M_Vero Air_FST/17.05.2
7

Publicité

loading