Electrical Characteristics - Mitsubishi Electric CITY MULTI PCFY-P15NKMU-E Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Electrical work
Types of control cables
1. Wiring transmission cables
Types of transmission cable
Shielding wire CVVS or CPEVS
Cable diameter
More than 1.25 mm
Length
Less than 200m (656ft)
. M-NET Remote control cables
Types of remote control cable Shielding wire MVVS
Cable diameter
0.5 (AWG 20) to 1.25 mm
Add any portion in excess of 10m (33ft) to
Length
within the longest allowable transmission cable
length 200m (656ft)
3. MA Remote control cables
Types of remote control cable 2-core cable (unshielded)
Cable diameter
0.3 (AWG22) to 1.25 mm
Length
Less than 200m (656ft)
SW1
ON
OFF
1 2 3 4 5 6 7 8 9 10
SW12
SW11
(10ths DIGIT)
(1s DIGIT)
Fig. 6-6

6.7. Electrical characteristics

Model
PCFY-P15NKMU-E
PCFY-P24NKMU-E
60Hz
PCFY-P30NKMU-E
PCFY-P36NKMU-E
2
(AWG16)
(AWG16)
2
2
(AWG16)
SWA
3
2
CN43
1
CN82
SWC
SW14
. /
.
(BRANCH No.)
Power supply
Hz
Volts
208 / 230V
6.4. Setting addresses (Fig. 6-6)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11 (for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
A Address board
6.5. Switch setting for different ceiling heights (Fig. 6-6)
With this unit, the air flow rate and fan speed can be adjusted by setting the SWA
(slide switch). Select a suitable setting from the table below according to the instal-
lation location.
* Make sure the SWA switch is set, otherwise problems such as not getting cool/
warm may occur.
SWA
3 (high ceiling)
P15, P24
11.5 ft. (3.5 m)
P30, P36
13.8 ft. (4.2 m)
SWA: Initial setting: 2 (Standard)
6.6. Sensing room temperature with the built-in sensor
in a remote controller (Fig.6-6)
If you want to sense room temperature with the built-in sensor in a remote
controller, set SW1-1 on the control board to "ON". The setting of SW1-7 and
SW1-8 as necessary also makes it possible to adjust the air flow at a time when
the heating thermometer is OFF.
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
Voltage range
MCA (A)
0.44 / 0.44
0.52 / 0.52
198 to 253V
1.04 / 1.04
1.22 / 1.22
2 (standard)
1 (silent)
8.9 ft. (2.7 m)
8.2 ft. (2.5 m)
9.8 ft. (3.0 m)
8.5 ft. (2.6 m)
FLA: Full Load Amps
Output: Fan motor rated output
IFM
Output (kW)
FLA (A)
0.090 / 0.090
0.35 / 0.35
0.095 / 0.095
0.41 / 0.41
0.160 / 0.160
0.83 / 0.83
0.160 / 0.160
0.97 / 0.97


Publicité

Chapitres

Table des Matières
loading

Table des Matières