WIKA SA-11 Mode D'emploi page 17

Masquer les pouces Voir aussi pour SA-11:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Commissioning, operation
Fitting a DIN 175301-803 A angular connector
1. Loosen the screw (1).
2. Loosen the cable gland (2).
3. Pull the angle housing (5), with the terminal block (6) inside, away from the
instrument.
4. Via the mounting hole (D), lever the terminal block (6) out of the angle housing (5).
Do not try to push the terminal block (6) out using the screw hole (1) or the cable
gland (2), otherwise the sealing of the angle housing could be damaged.
5. Select a conductor with an outer diameter matched to the angle housing's cable
bushing. Slide the cable through the cable gland (2), washer (3), gland seal (4)
and angle housing (5).
6. Connect the cable ends to the appropriate connection terminals on the terminal
block (6) (see table "Electrical connection").
7. Press the angle housing (5) onto the terminal block (6).
8. Tighten the cable gland (2) around the cable. Make sure that the seals are not
damaged and that the cable gland and seals are correctly seated in order to
ensure ingress protection.
9. Place the flat, square gasket over the pressure transmitter's connection pins.
10. Slide the terminal block (6) onto the pressure transmitter's connection pins.
11. Secure the angle housing (5) and terminal block (6) to the pressure transmitter
with the screw (1).
WIKA operating instructions pressure transmitter, model SA-11
(D) Mounting hole
(1)
(2)
(5)
(3)
(4)
(6)
17
EN

Publicité

Table des Matières
loading

Table des Matières