Télécharger Imprimer la page

Vaillant airMONITOR 0020245425 Notice D'emploi page 52

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 77
4 Installation
3.3 Information on the
identification plate
The identification plate is located on the
rear of the product.
Information on the
identification plate
working voltage
power consumption
supervisor
4 Installation
4.1 Checking the scope of delivery
Check that the scope of delivery is com-
plete and intact.
Quant-
Description
ity
1
CO monitor
1
Hanging bracket
1
Bag with connection material
1
Bag with fastening material
1
Enclosed documentation
4.2 Requirements for the
installation site
General requirements
Ensure that all of the LEDs are visible
after the installation.
Install the product with a minimum
clearance of 150 mm from the ceiling.
Install the product between 1 and 3 m
away from the heat generator.
Note that the following installation sites
are not permitted:
– Above a sink
– In cabinet-type casing
– Directly beside a door, a window, a fan
or a ventilation opening
– In locations at which the sensor is
blocked by dirt or dust
– In a moist environment
– Close to hobs
50
Meaning
Mains voltage and
mains frequency
Power consumption
Customer
– Close to electromagnetic fields
– In locations at which the operating tem-
perature cannot be maintained
Additional requirements for a room
that has a partition
Install the product on the same side of
the room as the heat generator.
4.3 Dimensions
4.4 Opening the product
B
Open the product as shown in the illus-
tration.
Installation instructions airMONITOR 0020234540_02
96
A
45

Publicité

loading