REQUEST PAGE: shows and allow to change kind and status of the request. The kind of the request and the
request by display can be set pressing ENTER and then button ↑↓ to change the values and then ENTER again
to save:
AUTO: Request by probes;
RC: Request by remote control;
BMS: Request by modbus;
ALARM PAGE: the simultanouesly pressing of button ALARM+↓ allow to visualise if there are alarms active on
the machine. when the alarmi s active it will take value 1.
Warning: in case of low pressure alarm occurs more than three times in one hour the machine will stop. To
reset di alarm press button ALARM for 5 seconds.
The machine can be enable by display, remote control (throught dry contact) and modbus
Until the machine will not be enable the compressor cannot start.
The choice of the kind of enabling can e made by display or modbus.
-
DIS: Enabling by display;
-
RC: Enabling by controllo remoto;
-
BMS: Enabling by modbus;
After the enabling on the display will appear the symbol ON.
To enable the unit from the main page push key arrow down↓ until the enable page:
Press ENTER in order to change the kind of enabling::
CS
M.CS830-00 ITA-ENG 08/11/2021