A - Electric power line
B - FLASH flashing indicator output
C - Antenna cable
D - ECSbus devices cable
- STOP input
- SbS input
E - Motors M1 and M2 output
Note 1 - You may use a cable longer than 30 m, provided it has a larger gauge (for example, 3 x 2.5 mm
automation, safety grounding.
Note 2 - For the ECSbus cables and the STOP and SbS input cables, you can also use a single cable with more internal conductors, to group
multiple connections.
WARNING! – The cables used must be suited to the installation environment.; for example a cable type H03VV-F is recommended
for indoor environments, and a cable type H07RN-F for outdoor environments is recommended.
1
CLB207
a
2
A
4 – English
star
combined
TABLE 2 – Technical specifications of electric cables
Cable type (minimum gauge values)
Cable 3 x 1.5 mm
Cable 2 x 1 mm
RG58 type shielded cable
Cable 2 x 0.5 mm
Cable 2 x 0.5 mm
Cable 2 x 0.5 mm
Cable 3 x 1 mm
b
FL200
c
PH200
e
IN100
d
B
C
D
E
D
Maximum admissible length
30 m (note 1)
2
6 m
2
20 m (less than 5m recommended )
20 m (note 2)
2
20 m (note 3)
2
20 m (note 3)
2
10 m
2
PH200
IN100
d
) and it is equipped with, close to the
2
c
e
d
D