Elektrischer Anschluss
Electrical Connection
Electrical Connection to ETAMATIC
Electrical connection
VDE and EVU specifications have to be observed when connecting
our actuator motors. Connections are to be executed by an
authorized specialist only. Please follow the connection diagram
glued to the inside of the top as well as the technical information
found on the outside of the actuating drives. All functions like end
switches, potentiometers and other options are ready wired.
The DPS outputs of ETAMATIC are suitable for a continuous
current up to max. 50mA. Motors with higher power consumption
can only be operated with an additional circuit to ETAMATIC.
Otherwise, the output of ETAMATIC will be destroyed.
These includes:
-
30Nm motors with a supply voltage of AC115V
-
30Nm motors with a running time of 30sec./90°
Additional parts
2x Signalconverter Interface AC230V / DC24V, 1-phase
Order no. 660R0028 (230VAC) 660R0029(115VAC)
1x Relay module with 2 relays to control the pos. of an actuator
up to 80 mA
Order no. 660R0013
Kap. 4