2.1
Energy count mode
4 possibilities of energy count
selects count type
confirms
ASYn
Partial energy count always on
SYn
Partial energy count activated by 2 active digital inputs with common point
Terminals 23-25
partial active energy count
Terminals 22-25
partial reactive energy count
Inputs type 2 EN61131-2 max. 27V direct current
Symbols
Count
inhibitedo
Count
active energy
Count
reactive energy
Count
active and reactive energy
trFS
Tariff count subdivided on 4 registers. Tariff switching with 2 active digital inputs,
with common point
Terminal 23
Symbols
23
Tariff 1
c
°
Tariff 2
^
c
Tariff 3
c
Tariff 4
c
Input terminals, tariff switching
Cntr
Partial energy count always on
Pulse metering from 2 active digital inputs, with common point
Terminals 23-25
input 1
Terminals 23-24
input 2
Max. input voltage: 27V
Max. input pulse frequency: 15Hz
07/18 E07 10782956 WEB E cod.MFD44..
23
24
25
c
0
0
c
0
1
c
1
0
c
1
1
24
25
0
0
0
1
1
0
1
1
E1
C
25 23
Terminal 23
2.2
External CT ratio
Ct =
external primary/secondary CT ratio
External CT ratio (Ct): 1...9999
moves the cursor
increases/decreases the loaded value
confirms
External VT ratio
Vt =
external primary/secondary VT ratio
External VT ratio (Vt): 1,00...10,00
For voltage direct connection (with external voltage transformer) load
Vt=1,00
By modifying the
reset
moves the cursor
increases/decreases the loaded value
confirms
E2
24
(ex.: CT 800/5A Ct = 160)
(max. primary current 50000/5A - 10000/1A)
(ex.: TV 600/100V Vt = 6)
(max. primary voltage TV 1200V)
CT
and/or
VT
ratios, the KWH meters are automatically
Nemo D4-Le