3.
Connect the other end of the grounding lug wire to a grounding point at your
site.
To connect DC power feeds to the terminal blocks:
1.
Loosen the retaining screws on each terminal block.
2.
Insert the 0V DC (positive voltage) return wire into the center COM connector
and the -48V DC power feed wire into either the left or right connector.
3.
Fasten the screws over the connectors.
4.
Turn on the power switch.
Note:
them are off, the Alarm LED on the management module glows red. This
warning indicates that maximum system reliability requires all installed power
supplies to be operational.
NetScreen-ISG 2000
If there are multiple power supplies in the NetScreen-ISG 2000 and any of
Installing and Wiring a DC Power Supply
19