AERASGARD
KLQ - SD / KLQ - W
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free duct sensor AERASGARD
determining the air quality (0...100 % VOC). The measuring transducer converts the measured values into a standard signal of 0 -10 V.
Maintenance-free duct sensor AERASGARD
locking screws, for determining the air quality (0...100 % VOC). The measuring transducer converts the measured values into a standard signal of
0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air
due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions etc. With regard to the
expected air contamination, low, medium or high VOC sensitivity can be selected. As an alternative, use IAQ categories (from excellent to unhealthy)
following the guidelines of the German Federal Environmental Agency to assess the room air.
TECHNICAL DATA
Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Service life:
Gas exchange:
Warm-up time:
Response time:
Ambient temperature:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
AERASGARD
®
KLQ - SD Duct air quality sensor and measuring transducer, Standard
®
AERASGARD
KLQ - W
Type ⁄ WG02
Measuring Range
VOC
KLQ - SD
K L Q - S D - U
0...100 %
KLQ - W
0...100 %
K L Q -W
Optional:
Cable connection with M12 connector according to DIN EN 61076-2-101 (on request)
Note:
This unit must not be used as safety-relevant device!
®
KLQ-SD with active output, automatic calibration, in a compact plastic housing with snap-on lid, for
®
KLQ-W with active/switching output, automatic calibration, in a compact plastic housing with quick-
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
VOC sensor (metal oxide) (VOC = volatile organic compounds),
with manual calibration (via zero button),
with automatic calibration (permanently active)
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivities (low/medium/high) or IAQ category (Indoor Air Quality)
(0 V = clean air, 10 V = polluted air)
KLQ - SD
0 -10 V (fixed)
KLQ - W
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
KLQ - SD
without changeover contact
KLQ - W
with potential-free changeover contact (24 V / 1 A), switchpoint adjustable
typically ± 20 % of final value (referred to calibrating gas)
> 60 months (under normal load conditions), depending on the type of loading and gas concentration
by diffusion
approx. 1 hour
approx. 1 minute, minimum flow rate 0.3 m / s (air)
–10...+60 °C
2
0.14 - 1.5 mm
, via terminals
plastic, UV-resistant, material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016),
KLQ - SD
with snap-on lid,
KLQ -W
with quick-locking screws (slotted ⁄ Phillips head combination)
72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
TM
PLEUROFORM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
by mounting flange, plastic (included in the scope of delivery)
III (according to EN 60 730)
KLQ - SD IP 54 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)
KLQ - W IP 65 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
*Housing in the built-in state (permeable PLEUROFORM: IP 30)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
Duct air quality sensor and measuring transducer, Premium
Output
VOC
(fixed)
0 -10 V
(switchable)
0 -10 V ⁄ 4...20 mA
= 30 m/s (air)
max
Equipment 
changeover contact
Rev. 2021 - V35
Item No.
IP 54
1501- 3170-1001- 500
IP 65
1501- 3150- 7301-500