FIREPLACE FRAMING AND INSTALLATION (CONT'D)
Solid fuels shall not be burned in this fireplace.
The maximum gas inlet supply pressure is 11 in. for Propane
and 10.5 in. for Natural.
For fireplaces for fixed fuel piping system and equipped with
a fireplace gas pressure regulator, the required manifold
pressure in inches water column: 11 in. for Propane and
4.5 in. Natural.
For fireplaces for fixed fuel piping system and equipped with
a fireplace gas pressure regulator, the fireplace and its indi-
vidual shutoff valve must be disconnected from the gas sup-
ply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psi (3.5 kPa).
The fireplace must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
Check all local codes for requirements, especially for the size and
type of gas supply line required.
RECOMMENDED MINIMUM GAS PIPE DIAMETER
Schedule 40 Pipe
Pipe
Inside Diameter
Length
Natural
0-10 feet
1/2 in.
0-3 meters
12.7mm
10-40 feet
1/2 in.
4-12 meters
12.7mm
40-100 feet
1/2 in.
13-30 meters
12.7mm
100-150 feet
3/4 in.
31-46 meters
19mm
NOTE: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing.
NOTE: Because some municipalities have additional local codes,
consult your local authority and installation code.
Installing a Manual Gas Shut-Off
Each fireplace must have an accessible manual gas shut-off located
in the vicinity of the unit. Where none exists, or where its size or
location is not adequate, contact your local authorized installer for
installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Fireplace must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
fireplace connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required by
the National Fuel Gas Code that a drip line be installed near the gas
inlet. This should consist of a vertical length of pipe tee connected
41308-2-0620
GAS SUPPLY
Tubing, Type L
Outside Diameter
Propane
Natural
Propane
3/8 in.
1/2 in.
3/8 in.
9.5mm
12.7mm
9.5mm
1/2 in.
5/8 in.
1/2 in.
12.7mm
15.9mm
12.7mm
1/2 in.
3/4 in.
1/2 in.
12.7mm
19mm
12.7mm
1/2 in.
7/8 in.
3/4 in.
12.7mm
22.2mm
19mm
into the gas line that is capped on the bottom in which condensation
and foreign particles may collect.
The use of the following gas connectors is recommended:
— ANSI Z21.24 A ppliance Connectors of Corrugated Metal Tubing
and Fittings
— ANSI Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction The Commonwealth of Massachusetts requires
that a flexible appliance connector cannot exceed three feet in length.
LP GAS
SUPPLY
SHUT-OFF
FEMALE NPT to
VALVE
FEMALE NPT
NATURAL
NATURAL
GAS SUPPLY
GAS SUPPLY
MALE NPT to
SHUT-OFF
FEMALE NPT to
MALE FLARE
VALVE
FEMALE NPT
NOTE: Gas shut-off shown. Other valves approved to use with
gas allowed.
Flex tubing to valve is pre-installed at the factory. Flare connector
is located in the envelope.
An accessible manual gas shut-off valve must be installed
external to the fireplace.
LP GAS
MALE NPT to
SUPPLY
MALE FLARE
MALE NPT to
FLEX TUBING
VALVE
MALE FLARE
NIPPLE
MALE NPT to
MALE FLARE
FLEX TUBING
REGULATOR
Figure 22
VALVE
Page 17