Typical Chimney Installation - Napoleon HIGH COUNTRY NZ6000-1 Instructions D'installation Et D'opération

Masquer les pouces Voir aussi pour HIGH COUNTRY NZ6000-1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

16
4.2

TYPICAL CHIMNEY INSTALLATION

EN
STORM COLLAR
ROOF FLASHING
ATTIC INSULATION
SHIELD
STRAIGHT CHIMNEY
* The fi rst fl ue offset closest to the top of the appliance must be a minimum distance of 12" (304.8mm)
from the top of the appliance.
1.
Move the appliance into position. Try to center the exhaust fl ue of the appliance,
midpoint between two joists to prevent having to cut them. Use a plumb bob to
line up the centre.
2.
Cut and frame an opening in the ceiling to provide a
minimum clearance of 2" (50.8mm) between the
outside of the chimney and any combustible material.
DO NOT FILL THIS SPACE WITH ANY TYPE OF
MATERIAL! Nail headers between the joists for extra
support. Firestop spacers must be placed on each
framed opening in any fl oor or ceiling that the chim-
ney passes through.
3.
Hold a plumb bob from the underside of the roof
to determine where the opening in the roof should
be. Cut and frame the roof opening maintaining
proper 2" (50.8mm) clearances.
NOTE: 30° or 45° offsets may be installed back to
back.
W415-1501 / 05.15.15
RAIN CAP
STORM COLLAR
ROOF FLASHING
ATTIC INSULATION
SHIELD
15 FT
(4.6m)
MINIMUM
34 FT
(10.4m)
MAXIMUM
OFFSET
SUPPORT
SINGLE OFFSET
CHIMNEY
RAIN CAP
STORM COLLAR
ROOF FLASHING
ATTIC INSULATION
SHIELD
15 FT
(4.6m)
MINIMUM
CEILING RADIATION
34 FT
(10.4m)
MAXIMUM
FIRESTOP
12" (304.8mm)
MIN*
DOUBLE OFFSET
HEADERS
FIRESTOP SPACER -
UNDERSIDE OF JOIST
2"
2"
(50.8mm)
(50.8mm)
Min.
Min.
Typical Joist Framing
RAIN CAP
15 FT
(4.6m)
MINIMUM
34 FT
(10.4m)
MAXIMUM
SHIELD
OFFSET
SUPPORT
FIRESTOP
12" (304.8mm)
MIN*
CHIMNEY
2" (50.8mm)
Min.
2"
(50.8mm)
Min.
Typical Roof Joist Framing
63.5A

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Nz6000-1

Table des Matières