10 – Display and Confi guration
10-11 Local Setup Menu
From the "AUDIBLE" screen, use the scroll buttons (
6
select the desired settings for the audible alarm and press the enter
button (
) to confirm the setting.
From the "DISPLAY" screen, use the scroll buttons (
7
select the desired LCD contrast setting and press the enter button
(
) to confirm the setting. Note: Changing this setting does not
require an administrator login – a user login is sufficient.
From the "LANGUAGE" screen, use the scroll buttons (
8
to select the desired setting and press the enter button (
confirm the setting. Note: Changing this setting does not require
an administrator login – a user login is sufficient.
9
From the "SERIAL COM ID" screen, use the scroll buttons
( , ) to select the desired serial port ID and press the enter
button (
) to confirm the setting. Note: This setting does not
apply to standard RS-232 connections. It only applies for RS-485/
RS-422 communications.
Note: Press the "ESC" button to return to the previous menu.

10-12 Maintenance Menu

Press the enter button (
) to select "MAINTENANCE" from
1
the main menu. Follow the login procedure described in step 2 and
step 3 of
Section
10-7.
2
After the correct password has been entered, the LCD screen will
show the maintenance menu. Use the scroll buttons ( , ) and the
enter button (
) to select a menu choice.
(continued)
(continued)
, ) to
, ) to
, )
) to
6
7
8
9
1
2
41
1
2
3
4
5
6
7
8
9
10
11
12
13
14