5.3.4
Relay output
The output signal of the control unit is made available via a voltage-free
relay contact (changeover contact). The alarm signal can be transmitted
to additional equipment.
1. Connect the additional equipment to the terminals "Alarm".
VOLTAGE PEAKS WHEN INDUCTIVE CONSUMERS ARE SWITCHED OFF
When inductive consumers are switched off, this can cause voltage peaks and
can lead to adverse effects on electrical systems and may destroy the switching
contact.
•
Use commercially available standard RC combinations such as
0.1 μF/100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.