Advanced Installer Setup
Honeywell has already programmed this control to work properly in most applications. However, you can adjust
the advanced settings by following the steps below.
To begin, press and hold the p and LIGHT buttons until
the display changes.
1 System Type
4 Control Mode
Automatic Mode is Default when Outdoor Sensor Detected
Manual Mode is Default when NO Outdoor Sensor Detected
5 Automatic Mode RH% (Hum)
This is the humidity setpoint (RH%) the control will operate to.
The homeowner does not change this and will only need to set
the appropriate window protection setting.
11 Automatic Mode Humidity Boost
Increases Preset RH% (#5) when user sets window protection
to 11.
17 Automatic Mode High Temp Shut-Off
Turns humidifier OFF when Outdoor Temperature is greater
than selected setting.
19 High Hum Limit
20 Low Hum Limit
21 High Dehum Limit
23 Low Dehum Limit
25 Dehumidifier Compressor Lockout
30 Humidity Sensing Calibration
This feature will offset the sensed indoor humidity.
35 Outdoor Temperature Sensor Calibration
This feature will offset the sensed outdoor temperature if
needed.
Humidifier 69-2413EF—09
1
Done
Next
Function Number
Press p or q to change settings.
Press NEXT to advance to the next function.
Press DONE to exit and save settings.
1
M29387A
Displayed
1
2
1
2
Range: 20%-60%
0
5%
10%
Range: 40° - 90°
Range: 10% - 90%
Range: 10% - 90%
Range: 10% - 90%
Range: 10% - 90%
Default = 0 Minutes (OFF)
Range: -9% to +9%
Default = 0 (Displays Actual RH%)
Range: -9° to +9°
Default = 0 (Displays Actual
Outdoor Temp)
Setting
Description
Humidifier
Dehumidifier
Automatic
Manual
Default = 35%
OFF
5%
10%
0 = OFF
Default = 65°
Default = 60%
Default = 10%
Default = 80%
Default = 40%
0 - 5 Minutes