Wiring And Safety Guidelines; Mounting The Terminal; Mounting Dimensions - Rockwell Automation Allen-Bradley PanelView 300 Instructions D'installation

Masquer les pouces Voir aussi pour Allen-Bradley PanelView 300:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

6
PanelView 300 Micro Terminal

Wiring and Safety Guidelines

Install the PanelView 300 Micro terminal using publication 70E, Electrical
Safety Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, follow these recommendations:
• Route incoming power to the PanelView 300 Micro by a separate path from
the communication cable.
• Where power and communication lines must cross, they should cross at right
angles. Communication lines can be installed in the same conduit as low level
DC I/O lines (less than 10 Volts).
• Grounding minimizes noise from Electromagnetic Interference (EMI) and is a
safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.
A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.

Mounting the Terminal

Enclosures
Mount the PanelView 300 Micro terminal in a panel or enclosure to protect the
internal circuitry. The terminal meets NEMA 12/13 and 4X (indoor use) ratings
only when properly mounted in a panel or enclosure with the equivalent rating.
Allow enough space within the enclosure for adequate ventilation. Consider heat
produced by other devices in the enclosure. The ambient temperature around the
PanelView 300 Micro must be between 0
Make provisions for accessing the side panel of the terminal for wiring,
maintenance and troubleshooting.

Mounting Dimensions

133 mm
(5.23 in.)
41061-156-01(A)
°
and 55
111 mm
(4.38 in.)
35 mm
(1.39 in.)
°
°
C (32
and 131
°
F).
48 mm
(1.87 in.)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

2711-m3a18l12711-m3a19l1

Table des Matières