3. Technical data ... / 4. Alarm contacts
Installation
Nominal position per EN 837-3 / 9.6.6 Figure 7: 90° (
n
Pressure connection: lower mount (LM)
n
In order to avoid any additional heating, the instruments must not be
n
exposed to direct solar irradiation while in operation!
Permissible vibratory stress at the mounting location
As a matter of principle the instruments should only be mounted at loca-
n
tions without vibratory stresses
Where required, a decoupling from the mounting location can be achieved
n
e.g. by a flexible connecting line from the measuring point to the pressure
gauge and mounting via a measuring instrument bracket.

4. Alarm contacts

EC-type examination certificates
Standard version Model 831.XX
n
PTB 99 ATEX 19 X (enclosure ) and ZELM 03 ATEX 018 X (enclosure 4)
Depending on the number of switches and on the case diameter either
Model SJ-N ... or Model SJ3.5- ... -N ... is used.
Safety pattern version Models 831.XX-SN or -S1N
n
PTB 00 ATEX 049 X (enclosure 3) and ZELM 03 ATEX 018 X (enclosure 4)
Depending on the number of switches and on the case diameter either
Models SJ -SN ..., SJ -S1N ..., SJ 3.5-SN ... or SJ 3.5-S1N ... are used.
The built-in sensor type is stated on the product label of the pressure gauge.
Wiring details
The electrical connections should be made by qualified electricians
n
Connection of the switches via screw terminals in the terminal box
n
Conductor cross section max. 1.5 mm
n
The terminal assignment is stated on the connection plate at the
n
pressure gauge
The instruments are to be included in the equipotential bonding of the plant
n
WIKA Operating instructions pressure gauges Model 63.51 with 831 per ATEX
)

GB
7