Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
Fuel
Fire size
Wax inhibitor (Clear 10) pan
0.09 m
fire
Anti-Foam (Surflo AF-300)
0.09 m
agent pan fire
Wood stack
0.09 m
n-Heptane pan fire
0.09 m
n-Heptane pan fire in direct
0.09 m
sunlight
n-Heptane pan fire in modu-
0.09 m
lated sunlight
n-Heptane pan fire in the pres-
0.09 m
ence of arc welding
n-Heptane pan fire in the pres-
0.09 m
ence of a 500 W lamp
Gasoline pan fire
0.09 m
JP4 fire
0.09 m
Methanol fire
0.09 m
Jet A-1 fire
0.09 m
The flame detector has three sensitivity settings to deliver flexibility in a
multitude of applications and to ensure detectors do not cross-vote.
The flame detector has, according to standard FM 3260, a high insensitivity to
frequent false alarms such as hot objects and hot work.
Instructions for use
|
Flame 1500
Distance
FM
certi-
fied
) pan 50 m (165 ft)
2
2
(1 ft
) pan 50 m (165 ft)
2
2
(1 ft
) pan 50 m (165 ft)
2
2
(1 ft
2
2
) pan 60 m (200 ft)
Yes
(1 ft
) pan 60 m (200 ft)
Yes
2
2
(1 ft
) pan 60 m (200 ft)
Yes
2
2
(1 ft
) pan 60 m (200 ft)
Yes
2
2
(1 ft
) pan 60 m (200 ft)
Yes
2
2
(1 ft
2
2
) pan 60 m (200 ft)
(1 ft
2
2
) pan 60 m (200 ft)
Yes
(1 ft
) pan 42 m (136 ft)
2
2
(1 ft
2
2
) pan 35 m (115 ft)
(1 ft
2.2.2

Field of view

The flame detector has a horizontal field of view of 90° and a vertical field of
view of 90°. The typical field of view and detectable range of a 0.1 m
Heptane pan fire at standard sensitivity is illustrated below. 100 % = 30 m
2.2.3
Advanced optical verification
There are three infrared emitters located on the fascia of the detector which
emit light onto the internal and external surfaces of the sapphire lens. The
reflections of IR light are continually monitored by the detector and if they are
disturbed by contamination on the inside or outside of the lens, the detector
signals an optical fault.
The optics of the flame detector can also be checked using the
Dräger FS-5000 Flame Simulator (serial number of J01001 onwards).
2.2.4
Explosive atmosphere protection
The flame detector is certified for use in some potentially explosive
atmospheres (see "Approvals", page 8). The explosion protection approval is
valid for use of the device in gas/vapour-air mixtures of combustible gases and
vapours under atmospheric conditions. The explosion protection is not valid for
use in oxygen-enriched atmospheres.
|