FUNCTION LIST
Circuit Board LED Indicators - JDF-2S (Early Models)
LED #
LED Color
1
Green
2 Cabinet
Red
3 Cabinet
Green
4 Bath
Red
5 Bath
Green
Illuminates:
When the compressor should be ON.
When the cabinet temperature is above 50 degrees F.
Flashes slowly when cabinet temperature exceeds 50 degrees F for 4
hours. Dispense functions are locked out under this condition. Power
down the dispenser to reset.
Flashes rapidly if dispense is attempted in lockout condition.
Open cabinet thermistor circuit will flash #2 and #3 LED's 1 time every 3
seconds.
Shorted cabinet thermistor will turn #2 and #3 LED's on steady.
When cabinet temperature is below 50 degrees F.
When bath temperature is above 34 degrees F.
Flashes slowly when compressor is in a 6 minute delay period.
Open bath thermistor circuit will flash #4 and #5 LED's 1 time every 3
seconds. The compressor will not run under this condition.
Shorted bath thermistor circuit will flash #4 and #5 LED's 2 times every 3
seconds. The compressor will not run under this condition.
When bath temperature is below 34 degrees F.
2
4
FIG 18 JDF-2S
(Early Models)
1
3
5
P3585
18
44744.2 062912