Lenze EMF2176IB Instructions De Montage page 17

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Design as isolation
Function
The CAN repeater automatically separates from a segment if the segment shows a
permanent disturbance level of +1 V ... +5 V between CAN-HI and CAN-LO. The
corresponding red LED is on. The other segment goes on working.
If the permanent disturbance level has disappeared, the segment is connected to the
system again through the CAN repeater.
Basic circuit diagram
CAN 2.1
HI
LO
GND
HI
LO
CAN 1.1 ... CAN 1.n
CAN 2.1 ... CAN 2.n
A total of max. 63 nodes possible
EDKMF2176X DE/EN/FR 4.2
Electrical installation
Design as isolation
CAN 2.n
GND
HI
LO
GND
Nodes in segment CAN1
Nodes in segment CAN2
HI
LO
GND
HI LO GND
CAN2
HI LO GND
CAN1
HI
LO
GND
HI
LO
GND
CAN 1.1
17
+24 V DC
=
(+9 ... +35 V DC)
+24 GND
2176
HI
LO
GND
HI
CAN 1.n
LO
GND
2176_002

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

33.2176ib

Table des Matières