Nidec Commander C200 Guide page 6

Masquer les pouces Voir aussi pour Commander C200:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Table 4-1
Protective ground cable ratings
Input phase conductor size
≤ 10 mm²
> 10 mm² and ≤ 16 mm²
> 16 mm² and ≤ 35 mm²
> 35 mm²
STEP 5: Remove the terminal cover and finger guard breakouts
1.
Using a flat bladed screwdriver, turn the terminal cover locking clip anti-clockwise by approximately 30°.
2.
Slide the terminal cover down.
3.
Remove terminal cover in direction shown.
6
Minimum ground conductor size
Either 10 mm² or two conductors of the same cross-sectional area as the input
phase conductor
The same cross-sectional area as the input phase conductor
16 mm²
Half of the cross-sectional area of the input phase conductor
1
2
Commander C200/C300 Step By Step Guide
3
Issue Number: 2

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Commander c300

Table des Matières