Special conditions
1. The I/O devices should be set up in such a way that the risk of mechanical danger is low.
2. The technical specifications of the I/O devices specified in the EU prototype test certificate must be adhered to:
Supply voltage of ET 200eco PN
Input and output currents
Ambient temperatures
3. M12 connectors (for PROFINET, supply voltage, encoders and actuators) must never be connected or disconnected with the
power on.
4. Use the following cables with even connector outlets to wire the different M12 interfaces:
PROFINET: SIEMENS, order number 6XV1 870-8A or 6XV1 871-5T
Supply voltage: SIEMENS, order number 6XV1 801-5D
Encoders and actuators: SIEMENS, Y-cable, order number 6ES7194-6KA00-0XA0; PHOENIX CONTACT *, product
designation SAC-3P-M12MS
5. All M12 connectors must be protected against unauthorized opening, for example with safety clips. Suitable safety clips are
available with PHOENIX CONTACT *, product designation SAC-M12-EXCLIP-F or SAC-M12-EXCLIP-M.
6. All unoccupied M12 circular sockets should be closed using sealing caps in such a way that the caps cannot be loosened by
hand (torque: 0.6 Nm). Suitable sealing caps are available from: Binder GmbH + Co. **, item no. 08 2769 000 000.
* PHOENIX CONTACT GmbH & Co. KG, Flachsmarktstr. 8, D-32825 D-Blomberg, http://www.phoenixcontact.com
(http://www.phoenixcontact.com)
** Binder GmbH & Co., Elektrische Bauelemente KG, Rötelstr. 7, D-74148 Neckarlsulm, http://www.binder-connector.com
(http://www.binder-connector.com)
Additional information on ET 200eco PN
You can find additional information on the ET 200eco PN distributed I/O device in the relevant operating instructions on the
Internet at the following link: ET 200eco PN operating instructions
(http://support.automation.siemens.com/WW/view/en/29999018)