Chassis Ground; Maintenance - Cotek SP Serie Manuel D'utilisation

Masquer les pouces Voir aussi pour SP Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Model
SP-700-112 / 212
SP-700-124 / 224
SP-700-148 / 248
SP-1000-112 / 212
SP-1000-124 / 224
SP-1000-148 / 248
SP-1500-112 / 212
SP-1500-124 / 224
SP-1500-148 / 248
SP-2000-112 / 212
SP-2000-124 / 224
SP-2000-148 / 248
SP-3000-112 / 212
SP-3000-124 / 224
SP-3000-148 / 248
SP-4000-124 / 224
SP-4000-148 / 248
Note! Batteries are capable of providing very large currents in
case of short circuit. The fuse should be as close to the positive
battery terminal as possible. Use Bussmann ANN series fuses (will
also require Fuse Block 4164) or equivalent.

3-2-4. Chassis Ground

Must be connected to earth ground prior to making any other connections
to the equipment.

3-3. Maintenance

Make sure that the fan vents are not blocked.
Use a vacuum cleaner to remove any dust from the fan area
When cleaning the case or front panel, use a soft, dry cloth, only. If the case
or front panel is very dirty, use a neutral, non-abrasive detergent. Do not
use alcohol or ammonia based solutions.
Regular service, and relocation of the inverter, should be performed by a
qualified service technician. Avoid spilling liquid on the inverter.
#6
#10
#16
#4
#8
#14
#1
#6
#10
#1/0
#4
#8
#4/0
#1
#6
#1/0
#4
Table 30. SP Series Wiring Cable diameter and Inline Fuse
Wire AWG
Inline fuse
≧150A
≧80 A
≧50 A
≧225A
≧125A
≧80A
≧350A
≧175A
≧90A
≧500A
≧225A
≧150A
≧700A
≧350A
≧175A
≧500A
≧275A
29