(3) Stick the soleplate of wired controller on the wall and then use screw M4×25 to
fix soleplate and installation hole on wall together;
(4) Insert the four-core twisted pair line into the slot of the wired controller and then
buckle the front panel and the soleplate of the wired controller together.
(5) Block the four-core wire into the groove at the left side of wiring column; bundle
the front panel of wired controller to its soleplate.
Note:
Separate the signal and communication lines of the wired controller from
the power cord and connection lines between the indoor and outdoor unit, with a
minimum interval of 20cm, otherwise the communication of the unit will probably
work abnormally.
If the air conditioning unit is installed where is vulnerable to electromagnetic
interference,then the signal and communication lines of the wired controller must
be the shielding twisted pair lines.
The 4-core terminal connects the air conditioner, while the 2-core terminal
connects the centralized controller. The connecting method for the 2-core connection
wire is same as that of 4-core connection wire.
No need to set the wire of wired controller into the clasp.

4.4 Disassembly

Fig. 24 Disassembly diagram for wired controller
Connect to either H1
terminal or H2 terminal.
As to which terminal
should be connected,
it depends.
24