Operation

The maximum permissible pressure loss in the supply lines to the overflow valve may not exceed
the 3% pressure dif ference between the set pressure and external back pressure on the ov erflow
v alv e.
Vibrations are to be av oided.
Check the f ollowing points prior to start-up:
All assembly and installation work are completed.
Compare the material, pressure, temperature and installation position with the lay out plan for
the pipework sy stem.
Dirt and residues f rom the pipeline and ov erflow v alve are removed to prevent leaks.
6.1
Adjusting device
Adjustable ov erf low valves 06001, 06198 and 06386
To set or correct the set pressure, adjust the set screw (2) of the overflow v alve.
To set the pressure:
Unscrew the cov er (1).
Remov e the USIT ring (3).
Loosen locknut (4) and suitably adjust the set screw (2).
Note the set pressure on the ty pe plate.
Clockwise rotation
Raises the set pressure.
Counter clockwise rotation
Lowers the set pressure.
When the desired pressure is set, secure the set screw (2) with t he locknut (4).
Put the USIT ring (3) in place again.
Screw on the cov er (1) again.
It is recommended to use manometers when adjusting the overflow valve.