10.2 Standard output ranges
Soldered jumpers are provided for the coarse setting of the
output ranges and the fine adjustment is accomplished using
the potentiometers "Zero" and "Span".
Soldered jumpers
Current
Channel
Channel
[mA]
1
2
0 ... 20
B120
B220
4 ... 20
B121
B221
± 20
–––
–––
10.3 Specific user output ranges
Units that have been configured for a specific user output
range cannot be subsequently reconfigured.
Span 2
Zero 2
Span 1
Zero 1
Fig. 6. Position of the soldered jumpers B..., potentiometers
"Zero" and "Span".

11. Mounting

The isolating amplifier SIRAX TV 808 is plugged onto a
backplane BP 902.
When deciding where to install the transmitter
(measuring location), take care that the limits of
the operating temperature are kept:
– 25 and + 40 °C for standard instruments!
Soldered jumpers
Voltage
Channel
Channel
[V]
1
2
B120
B220
0 ... 10
B122
B222
B123
B223
B121
B221
2 ... 10
B122
B222
B123
B223
B122
B222
± 10
B123
B223
11.1 Plugging the module into the backplane
Before inserting the SIRAX TV 808 into the
backplane, ensure that, ...
... the backplane wiring is in strict accordance
with the wiring diagram of the module
... the backplane is coded correctly ac-
cording to the section entitled "Mecha-
nical coding of the backplane". Read the
instructions for the back-plane.
... The red coding insert has been remo-
ved from the backplane for SIRAX plug-in
modules with a power supply of 24...60 V
DC/AC and that the power supply is correct
for the module.
1. Clip the module base onto the top-hat rail.
2. If the backplane is mounted vertically, turn the quick release
screws on the module to a vertical position, respectively if
it is mounted horizontally, turn the screws to a horizontal
position.
3. Press the quick release screws inwards with the screw-
driver until there is an audible click.
1.
Fig. 7. Plug the module into the base.

12. Commissioning

Switch on the measuring inputs and the power supply. The
green LED lights continuously after switching on.
The power supply unit must be capable of supp-
lying a brief current surge when switching on. The
isolating amplifier presents a low impedance at
the instant of switching which requires a current
I
of ...
start
≥ 160 mA for the version with a power supply
... I
start
range of 24 – 60 V DC/AC
or
≥ 35 mA for the version with a power supply
... I
start
range of 85 – 230 V DC/AC
2.
3.
19