4.8 - Simplified screen menu structure

NAVIGATION
Default screen
A
Factory password
FACTORY
Service password
SERVICE
User password
USER
Password = "0"
ALL

4.9 - Detailed menu description

4.9.1 - STATUS menu

Point
Description
MODE
Operating mode
hp_alarm
Heat pump alarm status
pulldown
Pulldown time delay
sanitime
Anti-legionella treatment time delay
OAT
Outside air temperature
HL1_CTRL
Control point, loop 1
BCK_CTRL
Control point, back-up heating
HP_CTRL
Heat pump control point
HP_EWT
Heat pump entering water temperature
HP_LWT
Heat pump leaving water temperature
HL1_TT
Tank temperature, loop 1
HL1_WT
Water temperature, loop 1
HL2_CTRL
Control point, loop 2
HL2_WT
Water temperature, loop 2
DHW_TT
Tank temperature, DHW
DHW_TT2
Temperature, additional DHW tank
DHW_WT
Domestic hot water temperature
DHW_BKWT Temperature, back-up DHW
DIST_EWT
Heat exchanger entering temperature, district heating nnn.n
DIST_LWT
Heat exchanger leaving temperature, district heating nnn.n
Notes Description
1
0
= Stop
1
= Heating
2
= Domestic hot water
3
= Anti-legionella treatment
4
= Anti-legionella treatment using back-up heating
100 = Quick test of the outputs
2
0
= No alarm
1
= Partial alarm
2
= Total alarm (complete stop of the heat pump)
3
Time delay for the emergency electric heater stages to start operating.
Password
Format Units
0-100
0-2
nnn
3
nnn
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
QCK_TEST

4.9.2 - SeTPOInT menu

Point
Description
-
hl1_stp
Setpoint loop 1
1
-
hl1_oat
Outside temperature threshold, loop 1 5.0 to 30.0
2
min
hl2_stp
Setpoint loop 2
min
dhw_stp Setpoint loop DHW
°C
dhw_hys Hysteresis DHW
dhw_low Low-temperature override DHW
°C
sani_stp Anti-legionella treatment setpoint
°C
freeze
Frost protection threshold
°C
°C
°C
4.9.3 - InPUTS menu
°C
°C
Point
Description
°C
SANI_SW
Remote anti-legionella treatment contact
°C
SUMM_SW Remote summer/winter contact
°C
°C
4.9.4 - OUTPUTS menu
°C
°C
Point
Description
HP_CMD
Heat pump control
°C
°C
HP_PUMP
External heat pump water pump
HL1_PUMP
Water pump loop 1
HL2_PUMP
Water pump loop 2
HL2_VLV
Mixing valve loop 2
DHW_PUMP DHW water pump
DHW_CHG
Change-over valve DHW/heating
DHW_VLV
Mixing valve DHW
DHW_BKP
Back-up pump DHW
DHW_WP
Pre-heating pump DHW loop
BACK_CMD Back-up heating control
EHS
Electric heater stages
ALR_REL
Alarm relay
RUN_REL
Unit operation relay
DIS_HVLV
Heating valve, district heating
DIS_DVLV
District heating valve for DHW
STATUS
SETPOINT
INPUTS
OUTPUTS
RUNTIME
ALARMS
CONFIG
OVERRIDE
MAINTAIN
SERMAINT
LOGOUT
Format
10.0 to 25.0
25.0 to 45.0
45.0 to 65.0
0.0 to 10.0
1.0 to 10.0
60.0 to 80.0
2.0 to 7.0
GENCONF
PUMPCONF
HL1_CONF
HL2_CONF
DHW_CONF
BKUPCONF
USERCONF
DATETIME
DISPLAY
CTRL_ID
FACTORY
Default Units
17.0
°C
17.0
°C
40.0
°C
55.0
°C
5.0
^C
10.0
^C
65.0
°C
5.0
°C
Format
Units
Closed/Open
-
Closed/Open
-
Format
Units
Start/Stop
-
On/Off
-
On/Off
-
On/Off
-
nnn
%
On/Off
-
On/Off
-
nnn
%
On/Off
-
On/Off
-
nnn
%
N
-
On/Off
-
On/Off
-
nnn
%
nnn
%
en
7
ENGLISH