Model C - Accessory HSM-00PPG000488200- heating control system type C
Heating system control (as accessory 00PPG000488100-)
with the possibility to obtain additional heating and
domestic hot-water production capacity from a district
heating system:
Allows control of a non-reversible heating system that
includes a 61WG heat pump and two different heat
emitter types and/or two independent comfort zones. For
optimised energy efficiency the heat pump is controlled by
a configurable weather compensation system.
Heating system example: with the possibility to obtain additional heating and domestic hot-water production
Heating system
GT4 P4 SV34
Floor heating
GT5
SV35
P5
Domestic hot
water in
Legend
Thermistors
GT1
Water temperature loop 1
GT1:3 Heat exchanger leaving water temperature, district heating
GT1:4 Heat exchanger entering water temperature, district heating
GT2
Domestic hot water tank temperature
GT3
Outside air temperature
GT4
Water temperature loop 2
GT5
Domestic hot water temperature
GT7
Additional domestic hot water tank temperature
GT7:2 Back-up heat exchanger temperature for domestic hot water
Pumps
P1
Pump for water loop 1 (radiators)
P2
External water pump for the heat pump
P4
Pump for water loop 2 (floor heating)
P5
Pump to re-heat the domestic hot water valve loop
P7
Pump for domestic hot water circulation
Valves
District heating heat exchanger valve for heating
SV21
District heating heat exchanger valve for domestic hot water
SV27
SV31
Three-way mixing valve for back-up heating
SV32
Heating/domestic hot water change-over valve
SV34
Three-way control valve for water loop 2
SV35
Three-way mixing valve for domestic hot water
capacity from a district heating system
P1
GT1
SV31
GT1:3
GT1:4
GT7:2
GT7
P7
The control box controls the heating and/or domestic
hot-water production support from a district heating
system. The control box supplies power to the circulating
pumps. Hot-water production can be permanent or
programmable with a second setpoint at the heat pump
and control of a switching valve.
GT3
SV21
SV27
SV32
GT2
Carrier 61 series
heat pump + HSM
P2
GT..
P..
SV..
Hot water
11
en
ENGLISH

Publicité

Chapitres

Table des Matières
loading

Table des Matières