INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7e
ALARM
The Sanicondens is fitted with an optional alarm control
cable, which should be connected as follows (see fig.
Reversing microswitch, not connected).
Depending on the alarm system selected (from 1.5 V to
220 V) use the blue wire
(contactor function) - maximum 0.5 A.
Warning! IIn the very rare case of an installation that cannot
operate temporarily without removal of condensates, it is
possible to use the brown wire
pilot the master relay (switch function).
In this case, if the alarm is triggered, the installation is
disconnected (contact our technical department for further
details).
Best: see fig.
7f
EXAMPLE OF AN INSTALLATION OF A SANICONDENS
7f
8
Check the state of the pellets regularly.
UNIT MAINTENANCE
Replace the pellets once a year. When replacing the
pellets, also clean the neutraliser drawer.
9
STANDARDS
Best conforms to the European directive
89/336/CEE on electrical safety.
SANICONDENS
®
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
1 0
DISASSEMBLY
If a breakdown occurs, any service on the unit should be
carried out by a qualified engineer. In particular the
replacement of the power cable.
Disconnect the electrical supply before carrying out
work on the unit.
and the brown wire
3
1
and the black wire
1
1 1
TROUBLESHOOTING
INSTRUCTIONS RESERVED SOLELY FOR
QUALIFIED PROFESSIONALS
7e
Disconnect the electrical supply before carrying out any work.
FAULT DETECTED
to
• The pump does not start
2
®
• The pump does not lift
1 2
GUARANTEE
parts and labour, subject to correct installation and use of
SANICONDENS
the unit.
PROBABLE CAUSES
• The pump is not
connected to the power
supply
• Power cut
• Float blocked
• Condensates inlet pipe
blocked
• Neutralisation drawer is
blocked
• Non-return valve blocked
• Discharge pipe blocked
Best SFA is guaranteed for 2 years for
®
ACTION NEEDED
• Plug in the unit.
• Check the mains voltage.
• Clean the SANICONDENS
®
Best tank.
• Clean the SANICONDENS
®
Best inlet pipe.
• Clean the drawer, replace
the pellets
• Clean the valve.
• Clean the discharge pipe.