Connecting the inverter
Caution – danger of electrocution!
e
If you wish to connect more than one user to the inverter and install
a socket distributor loop, you must arrange a circuit breaker (resid-
ual current circuit breaker) and set a grounding bridge in the
inverter, see chapter "Connect multiple appliances" on page 48.
When installed in vehicles or boats, the inverter must be connected to the
chassis or earth.
Before connecting, set the main switch (fig. 2 1, page 4) to "Off".
When setting up a socket distribution circuit (mains set-up), you must
comply with VDE 0100.
Only use copper cables.
Keep the cables as short as possible. The cables cannot be longer than
1.8 m.
After running the cable, secure it with cable ties to the clips on the cable
socket.
Keep to the required cable cross section and fit a cable fuse as close to
the battery as possible on the positive cable (see table).
Warning!
a
If you do not fit a fuse to the positive cable, the cables can over-
load, which might result in a fire.
Device
MSP 702
MSP 704
MSP 1012
MSP 1024
MSP 1512
MSP 1524
MSP 2012
MSP 2024
MSP 2512
MSP 2524
46
Required cable cross section
25 mm²
15 mm²
35 mm²
25 mm²
35 mm²
25 mm²
70 mm²
55 mm²
95 mm²
70 mm²
SinePower
Cable fuse
100 A
50 A
200 A
100 A
200 A
100 A
250 A
150 A
400 A
200 A