Victron energy MultiPlus Compact 12/2000/80 Manuel page 19

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Bulk Protection
When this setting is 'on', the bulk charging time is limited to 10 hours. A longer
charging time could indicate a system error (e.g. a battery cell short-circuit). Not
adjustable with DIP switches.
AC input current limit
These are the current limit settings at which PowerControl and PowerAssist come
into operation. The factory setting is 16A.
See Section 2, the book 'Energy Unlimited', or the many descriptions of this
unique feature on our website
www.victronenergy.com
.
Remark: lowest allowable current setting for PowerAssist: 2,7A.
(2,7A per unit in case of parallel operation)
UPS feature
If this setting is 'on' and AC on the input fails, the MultiPlus switches to inverter
operation practically without interruption. The MultiPlus can therefore be used as
an Uninterruptible Power Supply (UPS) for sensitive equipment such as
computers or communication systems.
The output voltage of some small generator sets is too unstable and distorted for
using this setting* – the MultiPlus would continually switch to inverter operation.
For this reason, the setting can be turned off. The MultiPlus will then respond less
quickly to AC input voltage deviations. The switchover time to inverter operation
is consequently slightly longer, but most equipment (most computers, clocks or
household equipment) is not adversely impacted.
Recommendation: Turn the UPS feature off if the MultiPlus fails to synchronise, or
continually switches back to inverter operation.
*In general, the UPS setting can be left 'on' if the MultiPlus is connected to a generator
with a 'synchronous AVR regulated alternator'.
The UPS mode may have to be set to 'off' if the MultiPlus is connected to a generator
with a 'synchronous capacitor regulated alternator' or an asynchronous alternator.
Dynamic current limiter
Intended for generators, the AC voltage being generated by means of a static inverter
(so-called 'inverter' generators). In these generators, rpm is down-controlled if the load
is low: this reduces noise, fuel consumption and pollution. A disadvantage is that the
output voltage will drop severely or even completely fail in the event of a sudden load
increase. More load can only be supplied after the engine is up to speed.
If this setting is 'on', the MultiPlus will start supplying extra power at a low generator
output level and gradually allow the generator to supply more, until the set current limit
is reached. This allows the generator engine to get up to speed.
This setting is also often used for 'classic' generators that respond slowly to sudden
load variation.
17

Publicité

Table des Matières
loading

Table des Matières