see-thru built out
note:
Shaded components (finish framing) must be
non-combustible materials
Finish framing must be built after the appliance has
been placed in its final position and venting
connected.
Drywall
minimum framing
Ref
LV38-1
E
16 3/16" (41.1cm)
N* / **
14 4/16" (36.2cm)
O*
25 11/16 (65.2cm)
P*
4" (10.1cm) Max
* Finishing material must be considered with the protrusion (i.e. P includes framing and
finish material). If desired, side and bottom protrusions can be done with 4" (10.1cm)
Max.
** This is a recommended dimension when mounting electronics above the appliance.
Otherwise, it can be as minimal as construction permits.
finish framing - after appliance installation
N
O
Insulation
LV50-2
LV62
16 3/16" (41.1cm)
16 3/16" (41.1cm)
14 4/16" (36.2cm)
14 4/16" (36.2cm)
25 11/16 (65.2cm)
25 11/16 (65.2cm)
4" (10.1cm) Max
4" (10.1cm) Max
Ceiling
E
note:
Although the minimum enclosure
LV74
height for the LV series is 73",
16 3/16" (41.1cm)
some venting configurations
14 4/16" (36.2cm)
that require more vertical rise
will require a larger enclosure to
25 11/16 (65.2cm)
provide minimum vertical clear-
4" (10.1cm) Max
ance between vent pipes and
combustibles.
W415-1709 / A / 07.27.17
EN
P*