Wayne CWS Série Instructions D'utilisation Et Manuel De Pièces page 6

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operating Instructions & Parts Manual
Operation
(Continued)
CONTROL VALVE SLOT
OPEN
Figure 11 - Control Valve
7. Close faucet and allow pump to
build pressure in tank. When the
pressure reaches the cut-out setting,
the motor will stop.
The system is now in operation and will
automatically cycle on demand.
PRIMING THE DEEP WELL PUMP
To prevent damage
to the pump, do not
start motor until pump has been fi lled
with water.
1. Remove prime plug.
2. Fill pump and piping completely full
of water.
3. Replace the prime plug.
4. Close the control valve (Figure 11)
and open a nearby faucet.
5. Start the motor. The pressure inside
the pump body will build almost
immediately as the pump, jet and piping
become completely filled with water.
6. Slowly open the control valve. Water
will begin to flow. Continue to open
the control valve until maximum flow
is achieved. Opening the valve too far
will cause the water to stop flowing.
7. Adjust the valve until there is a
steady flow of water. The valve
should be opened as much as
possible without losing pressure.
8. Let the system operate for several
minutes to flush all piping.
9. Close the faucets and allow the
pump to build pressure in the tank.
When the pressure reaches the cut-
out setting, the motor will stop.
The system is now in operation and will
automatically cycle upon demand.
Maintenance
Disconnect power
and release ALL
pressure from the system before
attempting to install, service, relocate
or perform any maintenance. Lock the
power disconnect in the open (off)
position. Tag the power disconnect
to prevent unexpected application of
power.
www.waynepumps.com
winter conditions.
DRAINING THE PUMP
1/4 IN.
Drain openings are provided on all
TURN
models. To drain the pump:
CLOSED
1. Remove drain plug and prime plug
to vent the system.
2. Drain all piping to a point below the
freeze line.
DRAINING THE TANK
Conventional tanks can be drained by
opening an outlet at the lowest point
in the system. Remove plug or the air
volume control to vent the tank.
Pre-charged tanks force virtually all
the water from the tank when system
pressure is released. No draining is
necessary.
RESTARTING PUMP
If the pump has been serviced, drained
or has not been used for some time,
be sure there is water in the pump
housing (volute) and the piping to the
well. There must be water in the pump
housing (volute) at all times when
the pump is running to avoid internal
damage of seal members (See Priming
the Shallow Well or Priming the Deep
Well Sections).
WATERLOGGED TANKS:
CONVENTIONAL
When a tank system has an inadequate
ratio of air and water, the pump will
start and stop often and erratically.
1. Disconnect the power to the pump.
2. Open the lowest faucet in the system
to release all pressurized water in
the system.
3. Prime the pump (See Priming the
Shallow Well or Priming the Deep
Well Sections).
4. Reconnect the power to the pump.
NOTE: As the pump refills the tank with
water, the air volume control supplies
the tank with the correct air to water
ratio for the system to operate. If the air
volume control is good, the pump will
shut off at the desired cut-off and will
be adjusted correctly.
WATERLOGGED TANKS: PRE-
CHARGED
If a pre-charged tank becomes
waterlogged, the bladder is normally
leaking or broken.
Protect the pump
1. Test the tank by depressing the air
from freezing during
2. Replace the tank.
NOTE: Once a bladder is leaking or
broken, the bladder cannot be repaired.
The tank must be replaced.
PRE-CHARGED TANK
Some air is lost through the bladder in
any tank. To prevent tank failure, check
the tank pre-charge on a yearly basis.
1. Disconnect power to the pump
2. Open a faucet nearest the tank and
3. Measure the tank pre-charge at the
4. If necessary, adjust the pre-charge
LUBRICATION
The bearing used in the pumps are
lifetime lubricated at the factory and
require no additional lubrication.
REMOVING OLD SHAFT SEAL
pressure from the system before
attempting to install, service, relocate
or perform any maintenance. Lock the
power disconnect in the open (off)
position. Tag the power disconnect to
prevent unexpected application of
power.
1. Disconnect power to the pump
2. Open a faucet nearest the tank and
3. Remove the four cap screws holding
4. Separate the pump housing (volute)
5. Remove the two cap screws and
6. Remove the small end cap on the
7. With a large screwdriver, keep the
6
valve. The air valve will expel water
if the bladder is broken.
allow all water to drain from the tank.
valve stem using a tire gauge.
with an air pump 28 - 30 psi on 1/2,
3/4 and 1 HP pumps.
Disconnect power
and release ALL
allow all water to drain from the
tank.
the pump housing (volute) to the
motor (Figure 12, on page 7).
from the motor to expose the
diffuser and the seal plate.
diffuser from the seal plate to
expose the impeller.
end of the motor opposite the
impeller.
shaft from rotating and remove
the impeller with hand (standard
right hand thread). Be sure to hold
onto the cast iron seal plate when
removing the impeller from the
shaft.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cws50-1/2 hpCws75-3/4 hpCws100-1 hp

Table des Matières