7. Initial setting by remote controller

(1) Press the
INITIAL SETTING
(2) [DISPLAY
]
WATER TEMP
WATER TEMP
HEATING
HEATING ECO
No. 1*
* No.1 or No.2 is indicated in display
Press
button
to switch to the next parameter setting.
MODE
<Target temperature in heating mode>
WATER TEMP
Set target flow water temperature in Heating mode with [TEMP] buttons (
HEATING
<Parameters for Heating ECO mode>
Set following 4 parameters in HEATING ECO mode with [TEMP] buttons (
HEATING ECO mode= Weather compensation mode
Target flow water temperature varies according to the outdoor temperature.
No.1
Display
WATER TEMP
Display
HEATING ECO
No. 2
Display
WATER TEMP
Display
HEATING ECO
Press
button
ON/OFF
Note:
· Heating ECO mode sets the set temperature depending on the outdoor temperature.
· The parameters except the above 4 parameters cannot be set. (The characteristic is linear between the point A and B.)
· When the "EXTERNAL INPUT(analog signal)" is used, the "HEATING ECO MODE" is invalid.
<Target temperature in HOT WATER mode>
Set target flow water temperature in HOT WATER mode with [TEMP] buttons (
WATER TEMP
HOT WATER
<Target temperature in ANTI-FREEZE mode>
Set target flow water temperature in ANTI-FREEZE mode with [TEMP] buttons (
WATER TEMP
ANTI-FREEZE
<Target temperature in COOLING mode>
Set target flow water temperature in COOLING mode with [TEMP] buttons (
WATER TEMP
COOLING
22
button
for 3 seconds to activate the initial setting mode.
WATER TEMP
WATER TEMP
HEATING ECO
HOT WATER
No. 2*
.
shows target flow temperature.
shows outdoor temperature.
shows target flow temperature.
shows outdoor temperature.
to switch
alternately. (The blinking figure can be changed.)
WATER TEMP
WATER TEMP
ANTI-FREEZE
COOLING
and
)
and
)
FLOW TEMP.
No.1
No.2
and
and
and
˚C
˚C
TEMP.
ON/OFF
TEMP OFFSET
TEMP OFFSET
HEATING
COOLING
.
.
A
B
OUTDOOR TEMP.
No.1
No.2
)
.
)
.
)
.