Wiring
<Wiring procedure>
1) Strip the insulation from the wire (3/4inch (20mm)).
2) Connect the connection wires between the indoor and
outdoor units so that the terminal numbers match.
Tighten the terminal screws securely. We recommend a
flathead screwdriver be used to tighten the screws.
3) Be sure to match the symbols for wiring and piping.
4) Pull the wire lightly to make sure that it does not
disconnect.
5) Pass the wiring through the cutout on the bottom of the
protection plate and attach the protection plate.
6) After completing the work, reattach the service lid to its
original position.
Shape the wires so that there is
no lifting of the service hatch or
other structural parts.
CAUTION
• Precautions to be taken for power supply wiring. When using stranded
wires, make sure to use the round crimp-style terminal for connection to
the power supply terminal block.
Flat washer
Screw
• When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead.
I mproper work may cause heat and fires.
Ground
This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.
13
A
Round
crimp-style
terminal
Good
Wrong
Stripping wire at terminal block
Outdoor unit
Room
A
Room
C
Indoor unit
Room A
If the length of a connection wire
is 33ft (10m) or more, use AWG14 wire.
Room A
Room B
power supply
Room C
Room D
Screw
Round crimp-
style terminal
Screw
Flat washer
Good
Arrow view A
Strip wire end
to this point.
power supply
Room
B
Room
D
Be sure to use the dedicated circuits.
Circuit breaker
To room D
To room C
To room B
Use AWG 16 or AWG 14 wire for
the power supply and inter-unit
wires.
Use the specified wires and
connect them securely.
Round crimp-style
terminal
Screw
Flat washer
Flat washer
B
Round crimp-
style terminal
Wrong
Round
crimp-style
terminal
Excessive strip length
may cause electric shock
or current leakage.
Good
Wrong
Ground fault circuit
60Hz 208/230V
interrupter
Stranded
wire
Screw
Round crimp-
style terminal
Flat washer
Good
Screw
Flat washer
Round crimp-
style terminal
Wrong
Arrow view B