8.0 finish framing

finish framing
EN
WARNING
!
Risk of fire!
Maintain all specified air space clearances to combustibles. Failure to comply with these instructions may
cause a fire or cause the appliance to overheat.
Ensure all clearances (i.e. back, side, top, vent, mantel, front, etc.) are clearly maintained.
Do not build into this area -
(35.6cm) wide area centered along the front of the appliance. No combustibles are allowed.
84"
2134mm *
* Allow for finished floor and hearth thickness when setting these dimensions.
** When constructing the enclosure allow for finishing material thickness to maintain clearances.
Combustible materials may be installed flush with the front of the appliance but must not cover any of the black face-areas
of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.
28
W415-1596 / B / 10.12.18
it must be left clear to provide adequate clearance for the vent in this 14"
3 1/2"
89mm
MAX
14"
356mm
MIN
1 1/2"
38mm
MAX
NOTE: Three braces are
required (as nailers).
41 1/4"
1047mm *