10.5. Further Steps For Troubleshooting; Appendix; 11.1. Overview Of Individual Symbols - salmson Smart Control SC-L Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Fault: Dry-running protection tripped
Cause: Dry-running level reached
E62
Solution: Check the unit parameters and adjust where
necessary; Check the fl oat switches are working correctly
and replace them if necessary
Fault: High-water alarm triggered
Cause: High water level reached
E66
Solution: Check the unit parameters and adjust where
necessary; Check the fl oat switches are working correctly
and replace them if necessary
Fault: Overriding OFF
Cause: "External OFF" contact is open
E68
Solution: Use the "External off" contact according to the
latest wiring diagram; Check settings in menu 5.4.9.0 and
adjust them if necessary
Fault: Fault on the connected pumps
Cause: No feedback from the corresponding contactor
E80.x
Solution: Set the separate HAND-0-AUTO switch for the
pump shown to "Auto (A)"; Contact Salmson customer
service
Fault: Max. running time for the connected pumps
exceeded
Cause: Pump shown runs for longer than specifi ed in
E85.x
menu 5.4.6.0
Solution: Check settings in menu 5.4.6.0 and adjust
these where necessary, request these from Salmson
customer service
Fault: Plausibility error
Cause: Float switches are in incorrect sequence
E90
Solution: Check installation and connections and adjust
these where necessary
".x" = info on the relevant pump to which the error shown refers!

10.5. Further steps for troubleshooting

If the points listed here do not rectify the fault, contact Salmson
Customer Service. They can help you as follows:
• Telephone or written support from Salmson Customer
Service
• On-site support from Salmson Customer Service
• Inspection or repair of the switchgear at the factory
Please note that you may be charged for some services provided
by our Customer Service. For more details, please contact Salmson
Customer Service.
11.

Appendix

11.1. Overview of individual symbols

Back (brief press: one menu level; long press: main
screen)
EASY menu
EXPERT menu
1. Description: Service not registered
2. Description: Display value – no entry possible
Service
Parameter
Information
Error
Reset error
Alarm settings
Error in power supply (phase error, incorrect rotating
fi eld, low voltage)
Error in motor winding (WSK, PTC, impermeability)
External Off
Pump
Pump 1
Pump 2
Pump 3
Pump 4
Pump cycling
Time-dependent pump cycling
Pump test run
Maximum pump running time
Setpoints
Activation and deactivation thresholds
Actual value
Sensor: Signal type
Sensor: Measurement range
51

Publicité

Table des Matières
loading

Table des Matières