Components description

Introduction
Cabinet
Filters
Heat exchanger
Fans
Bypass damper
Water outlet
Humidity sensor
10
This section describes the individual components of the HCV 400, which are part of standard
delivery .
The external parts of the cabinet are manufactured from powder coated, AZ-coated steel
plating . The internal parts of the cabinet are manufactured from expanded polystyrene (EPS) .
Accessories are installed after removing the steel front and EPS doors . The cabinet is sound
and heat insulated with fire retardant polystyrene foam . The unit is designed for installation in
ambient temperatures from 12° to 50°C .
The unit is equipped with a class G4 cassette filter as standard . These filters protect the heat
exchanger and improve the indoor climate by filtering the air of dust and other particles . An
F7 filter (pollen filter) can be purchased as an accessory . The F7 filter is always placed on the
supply side - shown on the top of the unit .
The reverse flow heat exchanger absorbs the heat energy from the evacuated air and moves
it to the fresh air, thereby saving on energy needed for heating .
The supply fan adds fresh air from outside through the heat exchanger to the ventilated
indoor rooms .
The extractor fan sucks out stale and moist air from the home through the heat exchanger,
where it releases its heat into the fresh outdoor air .
The motorized bypass damper overrides the heat exchanger functionality . This is used in
warm summer conditions, where colder outside air can be used for reducing inside tempera-
ture, when inside temperature exceeds an upper temperature limit .
The unit is equipped with two drain valves . One of these must be connected to a drain hose
to direct the condensate to a drain .
Correct connection to the drain valves is shown at the top of the unit and on page 20 in
this service manual .
The humidity sensor will continuously monitor the quality of the extract air, and adjust the air
flow level accordingly . This operation is named demand mode . If a HRC remote control is con-
nected, the level will be shown in the display using 3 level icon .
Using demand mode will result in the correct level of ventilation with lowest possible electri-
cal power consumption .