5.3 - STARTING
• Via the On/Off switch located on the remote control.
• Select one of the fan speeds using the switch on the remote control.
• Modify the adjustment of the temperature set point to check the operation and the direction of activation of the
regulation.
• Adjust the temperature setpoint value to the required value.
• Adjust the position of the deflection flaps if necessary.
Note:
A fuse on the printed circuit board next to the air handler's terminal board protects the circuits (see diagram)
Fuse rating : 2A - 250 V - F type (cut-off power: 60 A).
Fuse size
: 5 x 20.

6 - MAINTENANCE

Before doing any work on the installation, check that the power supply is switched off and secured.
• Air filter: Clean every two weeks. See "Operating Manual".
• Electric connections: Once a year, check that the electric wires are well fastened to their terminals.
• Electric box: Dusting is recommended once a year.
• Condensate pumping system: This requires regular specific maintenance.
The maintenance cycle is determined by the conditions of operation (minimum operations to be performed each time the
installation is restarted in cooling mode).
- Clean the condensate recovery tray located under the heat exchanger and check hoses/pipes.
Clean with water containing 5% bleach.

7 - WIRING DIAGRAM

10 05 618 - 02
MSW - Basic version
G
Grey
J
Yellow
L
Purple
M
Brown
Ventilation common circuit
O
Orange
P
Pink
W
White
C1 Capacitor of M1
F1 Control circuit fuse
M1 Fan
IMPORTANT
Power supply 230V/1/50Hz
U
N
4
Thermostat
power supply
1
3
Low speed
20
Medium speed
21
High speed
22
F1
2A
F
GB
I
E
D
C1
M1
9