4.3.4 - REMOTE CONTROL (accessories)
F
• 2 types:
- RAB 30 - Code K 60 D 076 Z with manual change-over (hot/cold toggling).
GB
- RCC 10 - Code K 60 D 051 Z with automatic change-over (hot/cold toggling).
I
E
Operating switch with fan
speed selection
D
Temperature setting knob
Heating / cooling selector switch
A - Montage / Installation
• See the main characteristics in the Technical Instructions (for the RCC).
• Consult the "Installation instructions" supplied with the control.
• The unit is connected using 0.75mm
• The cables used must comply with the insulation requirements for the voltage used (230V).
This information relates above all to the sensor input of the automatic control connected to the 230V supply.
• The temperature adjustment range can be limited by means of the mechanical limit stops located on the control knob.
Wall mounting:
• Secure the unit at a height of approximately 1.5 m from the floor in a location representative of normal convection
currents, while avoiding:
- wall which are poorly insulated or liable to vibrate,
- the proximity of parasitic heat sources (sunshine, heating appliances, lamps, fireplaces, televisions, etc.),
- currents of air from doors or windows,
- sheltered locations such as shelves or behind curtains,
- near electrical outlets.
• For manual control K 60 D 076 Z, check and modify as required the ventilation selection jumper connection SR
depending on the appliance (see below).
• For the RCC 10 controller (K 60 D 051 Z), check and possibly modify the settings of DIP switches 1 to 5 (located inside
the control) according to the application (refer to the indications below and the controller's technical manuals).
B - Connections with manual remote control RAB 30 - code K 60 D 076 Z
• Manual selection of the operating mode (heating or cooling).
• Control by action on the 230V "On/Off" valve and/or on ventilation.
Position of the SR bridge located inside the controller:
- on SR1
- on SR2 (Auto) = Ventilation actuated with the valve.
6
RAB 30
Control on a valve
Power supply 230V / 1 / 50Hz
K 60 D 076 Z
SR
L
SR1
Auto
Q1
SR2
Q2
Q3
Y2
Y1
= Permanent ventilation.
Heating on indicator light
Ventilation on indicator light
Cooling on indicator light
Temperature setting knob
2
2
cable (minimum) (1.5mm
N U
1
3
4
20
21
22
MSW
Valve
RCC 10
Operating switch with fan speed selection
max.).
Control on ventilation
Power supply 230V / 1 / 50Hz
K 60 D 076 Z
SR
L
SR1
Auto
Q1
SR2
Q2
Q3
Y2
Y1
Position of the SR bridge located inside the controller
on SR2 (Auto)
N U
1
3
4
20
21
22
MSW